Table 60: FB Name: SF_GuardLocking
Name
Data Type
Initial Value
Description, Parameter Values
VAR_INPUT
Activate
BOOL
FALSE
Table 31 “General Input Parameters”
S_GuardMoni-
toring
BOOL
FALSE
Variable.
Monitors the guard interlocking.
FALSE: Guard open.
TRUE: Guard closed.
S_SafetyActive
BOOL
FALSE
Variable.
Status of the hazardous area (EDM), e.g., based
on speed monitoring or safe time off delay.
FALSE: Machine in "non-safe" state.
TRUE: Machine in safe state.
S_GuardLock
BOOL
FALSE
Variable.
Status of the mechanical guard locking.
FALSE: Guard is not locked.
TRUE: Guard is locked.
UnlockRequest
BOOL
FALSE
Variable.
Operator intervention – request to unlock the
guard.
FALSE: No request.
TRUE: Request made.
S_StartReset
BOOL
FALSE
Table 31 “General Input Parameters”
S_AutoReset
BOOL
FALSE
Table 31 “General Input Parameters”
Reset
BOOL
FALSE
Table 31 “General Input Parameters”
Also used to request the guard to be locked
again. The quality of the signal must conform to a
manual reset device (EN954-1 Ch. 5.4)
VAR_OUTPUT
Ready
BOOL
FALSE
Table 32 “General Output Parameters”
S_GuardLocked
BOOL
FALSE
Interface to hazardous area which must be
stopped.
FALSE: No safe state.
TRUE: Safe state.
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017
AC500-S
318