Table 63: FB Name: SF_TestableSafetySensor
Name
Data Type
Initial Value
Description, Parameter Values
VAR_INPUT
Activate
BOOL
FALSE
Table 31 “General Input Parameters”
S_OSSD_In
BOOL
FALSE
Variable.
Status of sensor output, e.g., light curtain.
FALSE: Safety sensor in test state or demand for
safety-related response.
TRUE: Sensor in the state for normal operating
conditions.
StartTest
BOOL
FALSE
Variable.
Input to start sensor test. Sets "S_TestOut" and
starts the internal time monitoring function in the
FB.
FALSE: No test requested.
TRUE: Test requested.
NoExternalTest
BOOL
FALSE
Constant.
Indicates if external manual sensor test is sup-
ported.
FALSE: The external manual sensor test is sup-
ported. Only after a complete manual sensor
switching sequence, an automatic test is possible
again after a faulty automatic sensor test.
TRUE: The external manual sensor test is not
supported.
An automatic test is possible again without a
manual sensor switching sequence after faulty
automatic sensor test.
S_StartReset
BOOL
FALSE
Table 31 “General Input Parameters”
S_AutoReset
BOOL
FALSE
Table 31 “General Input Parameters”
Reset
BOOL
FALSE
Table 31 “General Input Parameters”
TestTime
TIME
T#10ms
Constant. Range: 0 … 150ms.
Test time of safety sensor.
VAR_OUTPUT
Ready
BOOL
FALSE
Table 32 “General Output Parameters”
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017