3.
Verify against your safety application technical specification that all iParameters for all Safety I/O chan-
nels are set correctly.
4.
Go to F-Parameter tab and press
“Calculate”
button. Copy calculated F_iPar_CRC value from the
“Checksum iParameter” field and paste it to F_iPar_CRC field of the F-Parameter editor (see below).
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification procedure workflow
30.03.2017
AC500-S
415