Installation
81
Aastra 415/430 as of R3.2
syd-0344/1.6 – R3.2 – 09.2014
4. 2. 2. 2
Aastra 415 rack-mounting set
Equipment supplied:
• 2 mounting plates for rack installation
• Screw set
4. 2. 2. 3
Aastra 430 rack-mounting set
Equipment supplied:
• 2 mounting plates for rack installation
• Screw set
• Fan
4. 2. 3
Location requirements
The following location requirements must be observed when positioning the com-
munication server.
Hazard
Failure to observe the location requirements can cause the communica-
tion server to overheat, damaging electrical components and/or the sur-
rounding area.
An event message is generated if the heat dissipation is insufficient.
Appropriate measures must be taken immediately to improve the heat
dissipation, e.g. by providing the required clearances, lowering the ambi-
ent temperature or installing the fan from the rack-mounting set (Aastra
430 only).
Tab. 34
Aastra 415/430 Location requirements
Heat radiation
• Do not position in direct sunlight, near radiators or near other heating sources
EMC
• Do not position in strong electromagnetic fields of radiation
(e.g.near x-ray equipment, welding equipment or similar).
Heat dissipation
• Do not place any objects on top of the communication server.
• Observe the clearance requirements for wall mounting and desktop installation (see
Fig. 12
and
Fig. 13
).
• In a rack-mounted installation the space to the left and right between the communication
server and the wall of the 19” rack must remain empty. The installation of a fan is also
mandatory for the Aastra 430.
Environment
• Ambient temperature 5 °C...45 °C
• Relative humidity 30…80%, non-condensing