Installation
87
Aastra 415/430 as of R3.2
syd-0344/1.6 – R3.2 – 09.2014
4. 2. 6
Desktop installation
To protect the cable connections the communication server can also be secured
using three screws. The same drilling plan (see
Fig. 14
) and the same procedure ap-
ply as for wall mounting (see
"Wall-mounting procedure", page 86
).
Warning
To ensure adequate heat dissipation make sure that no objects are placed
on top of the communication server (see also
"Location requirements",
page 81
). Minimum distances must also be observed as shown in
Fig. 12
.
4. 2. 7
Rack-mounting
The rack-mounting set Aastra 415 or Aastra 430 allows the communication server
to be installed horizontally into a 19” rack. Be sure to observe the following:
• The communication server takes up the space of 1.5 height units inside the 19”
rack. (1 Unit corresponds to 44.45 mm).
• The holes in the mounting plates allow two communication servers to be placed
directly above each other with a space requirement of three units. Different
holes in the mounting plates are used for this purpose (see
Fig. 16
).
• The space on the left and right between the communication server and the pan-
els of the 19” rack is for heat dissipation and must remain clear.
• The installation of a fan is mandatory whenever an Aastra 430 is rack-mounted;
the fan is included in the Aastra 430 rack-mounting kit.
Note: The rack-mounting set always includes fastening screws for the fan. On the
Aastra 415 these two screws are superfluous.