16.14.6
Motor brakes test
The function interrupts the safety circuit during travel. The distance covered by the cabin before
coming to standstill is shown in the display.
Information
The function is only possible in connection with CAN activation.
Perform motor brakes test
Power section
-> Checks
ZA-Intern
Select
"Checks"
menu
Checks
|
-
"
SCY_EN
OFF
|
-
"
ON
Enable tests
Select parameter
"SCY_EN"
Enter "SCY_EN=On"
Checks
|
-
"
SCY_MB
OFF
|
-
"
ON
Engine brakes test
Select parameter
"SCY_MB"
Switch on motor brakes test with "SCY_MB=ON"
Give travel command up with empty cabin
Interrupt safety chain
CAUTION!!!
Motor brakes test
active. Braking dist.
[ESC] 87 mm
Display distance up to standstill
16.15
Electronic name plate
With the "electronic name plate" function, you can
fi
le parameters from the ZETADYN 4 in an absolute
value encoder or load data from an absolute value encoder into the ZETADYN 4. The function is
possible in rotary encoders with EnDat, Codeface and Hiperface interfaces.
Save data
MMC Recorder
-> Encoder adjust.
Safety gear
HW. Ident.
Select menu
Encoder adjustment
Encoder-adjust.
|
-
"
SAV_P_E OFF
|
-
"
ON
Parameters on encoder
Select parameter
"SAV_P_E"
Enter "SAV_P_E=On"
Translation of the original operating instructions
ZETADYN 4C
Special functions
R-TBA12_01-GB 1415
Part.-No. 00163371-GB
186/204