During installation
•
Mount the device in a torsion free conditions
•
Installation position: vertical, connection terminals (X1, X2, X3) at bottom; no horizontal assembly
•
Mount the frequency inverter so that it is isolated
•
Prevent drilling chips, screws and other foreign bodies from reaching the interior of the frequency
inverter
•
Maintain the stated minimum clearances to ensure unobstructed cooling- air feed as well as
unobstructed outgoing air discharge (see
fi
g. "Minimum clearances")
Ambient conditions
•
It is not permitted to mount the frequency inverter on vibrating components
•
The frequency inverter must not be exposed to any shock
•
Prevent humidity
•
Avoid aggressive and conductive materials in the environment
4.1.1
Switch cabinet installation
CAUTION!
Caution!
The frequency inverter is designed for wall mounting in the machine room or elevator shaft. Adequate
cooling must be ensured for assembly in the switch cabinet. The power loss of the frequency inverter
(see chapter "Technical Data") must be taken into account here.
The speci
fi
ed installation position and the minimum distances must be observed when assembling in
the switch cabinet.
4.1.2
Wall installation
The ZETADYN 4C is mounted on the wall using a 3-point fastening.
"
Attach fastening screw for the upper fastening point.
1
1
Upper fastening point
"
Hang the ZETADYN 4C on the upper fastening point.
"
Mark the positions of the lower fastening points.
2
2
2
Lower fastening points
"
Drill the fastening holes (the ZETADYN 4C can be moved to the side and must not be removed).
"
Fix the ZETADYN 4C with one screw each at the lower fastening points.
Translation of the original operating instructions
ZETADYN 4C
Mechanical installation
R-TBA12_01-GB 1415
Part.-No. 00163371-GB
14/204