14.8
Automatic parameter check (APC)
The Automatic parameter check checks the input values for plausibility and tolerances while the
parameters are being entered.
The APC function aims to prevent erroneous parameter inputs. Every message must be acknowl-
edged by the user with the key
You can activate or deactivate the APC function in the
Monitoring/APC
menu. The factory setting is
ON.
Monitor
|
-
"
APC
ON
|
-
"
ON
Auto. parameter via
Through the APC function:
•
Values are restricted (Limit)
•
Parameters are set (Set)
•
Parameters are updated (Update). Parameters that are not preset are updated during a software
update.
14.9
Automatic parameter diagnostics (APD)
During Automatic parameter diagnostics, the following are checked:
•
The parameters for plausibility and tolerances
•
Device functions for functional errors
Erroneous parameters or functions are shown in the display.
Every message must be acknowledged by the user with the key. The APD function can be activated
in the
"Statistic/APD"
menu. After checking, the function is reset to "OFF".
Statistics
|
-
"
APD
OFF
|
-
"
ON
Automatic parameter
Translation of the original operating instructions
ZETADYN 4C
Error diagnosis
R-TBA12_01-GB 1415
Part.-No. 00163371-GB