9.9.4Save user settings restore with PIN 9090
Save User Setup
The individually made device con
gurations (User Settings) can be saved
and, with the corresponding PIN input (9091), can be reestablished.
By entering
PIN 9090
the individually made device con
gurations can be
reestablished (
F
Start - PIN Input).
Information
By entering
“
PIN 9095
”
in the
“
PIN
”
menu in the
“
start
”
menu-group, the device is entirely reset
to the pre-delivery condition.
Any changes that have been made to the settings are thus lost!
9.9.5
Sensor Alarm ON / OFF
Function only in controller mode (
2.01
)!
For
“
E1 Analog In
”
and if activated for sensor 2
“
E2 Analog In
”
.
In case of an interruption or short-circuit in the sensor conductor, or in case of measured values that
lie outside of the device
’
s measurement range, a time-delayed fault indication takes place.
Alarm sensors
With
“
Alarm Sensors
”
=
“
OFF
”
(factory setting). Indi-
cated sensor disturbances are displayed as
“
Message
”
alternating to the actual value and stored in the menu
of
“
Events
”
.
Sensor 1
Alarm sensors
With
“
AlarmSensors
”
=
“
ON
”
areindicated sensor distur-
bances as
“
Alarm
”
alternating to the actual value and
stored in the menu of
“
Events
”
.
Indication via relays is possible (
F
IO Setup / function
relay outputs).
Sensor 1
9.9.6
Limit
Limit
After allocation of a digital input (
F
IO Setup) an adjustable limitation of the
modulation can be activated via a digital input (
“
D1
”
,
“
D2
”
, ..).
As long as no allocation has been carried out
“
IO Setup
”
. Display:
|
- - -
|
“
Limit value
”
= max. possible modulation
(e.g. speed reduction during night opera-
tion by time switch).
Setting range:
“
Limit
”
=
“
n-max
”
up to
“
n-
min
”
.
Factory setting: 100 %
≙
max. modula-
tion, i. e. no limit.
Setting depending on device tye in: % or
rpm.
nM
50 %
100 %
D
P
Min.
L= 70% Min.= 0 % Max. = 100 %
50 %
R
0 %
I
S
100 %
I
L
L = 70% Min. = 35 % Max. = 85 %
10.05.2007
v_limit.vsd
Limit (idealized principle diagram)
nM Motor speed
L Limit
S Setpoint
R Pband
D Speed controller: setting signal
P P-controller: control deviation
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
49/85