9.10.3.8
Automatic control / speed manual, Function
|
7D
|
(mode
2.01
)
Switch over between automatic control to set target value (depending on the activation:
“
Setpoint1
”
,
“
Setpoint2
”
) and the default for
“
manual operation
”
set at the device.
If for Analog In 2
“
E2 function
”
is programmed to
|
2E
|
switch over between
“
Setpoint1
”
or
“
Setpoint2
”
and external manual operation. With activated manual mode the display constantly changes between
“
actual value
”
and value for
“
manual mode
”
.
Contact at digital input e.g.
“
Digital In 1
”
Controller
D1 D1
1
0
n = 0 -100 %
1
n = 80 %
0
- - - - -
- - - - -
- - - - -
Se
E1
EH
E2
11.05.2007
v_7d_regelung_hand.vsd
3
2
1
1 Setting
“
Setpoint1
”
2Setting
“
Setpoint2
”
3 Setting
“
Speed manual
”
(depending on device type in: %, Hz, rpm)
EH Signal for Manual mode extern, E2Function =
|
2E
|
Se Sensor
•
“
D1 Inverting
”
=
“
OFF
”
Automatic
control at opened contact / manual
operation at closed contact.
•
“
D1 Inverting
”
=
“
ON
”
: Automatic
control at closed contact / manual
operation at opened contact.
9.10.3.9
Reverse action of control function (
2.01
), Function
|
8D
|
Switchover between: Increasing modulation during increasing actual-value and increasing modulation
during sinking actual-value.
The factory presets for the
“
Control function
”
are dependent on the selected mode of operation (
F
Controller Setup - reverse operation of the control function).
When switching over via a digital input, the device works with the opposite function than the one set
there!
Val>Set=n+
Settings in Controller Setup
9.10.3.10
Reset, Function
|
10D
|
Reset after motor fault by using an non-locking reset key. The unit switches off when interruption
between both
“
TB/TP
”
or
“
TK/PTC
”
terminals, the unit then remains switched off (
“
motor fault
”
see
F
motor protection). Re-starting after the drive has cooled down (terminals
“
TB/TP
”
- or
“
TK/PTC
”
bridged) by non-locking reset key possible.
11.05.2007
v_10d_reset.vsd
Controller
D1 D1
Reset
TB/TP
Contact at digital input e.g.
“
Digital In 1
”
•
For
“
D1 Inverting
”
=
“
OFF
”
both
terminals
“
D1
”
-
“
D1
”
in normal oper-
ation interrupted. Reset after fault by
short close.(For
“
Inverting
”
=
“
ON
”
reverse function).
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
58/85