8 Start-up
8.1 Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Check all connections for correctness once more.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the fan's hazardous area.
8.2 Procedure for commissioning
Depending on software version and type of device function Motor OFF / ON is in menu group Start.
Display after
rst turning on the mains voltage.
In menu group
Start
the adjustment for
Motor
is
“
OFF
”
for factory setting.
This prevents the system from inadvertently starting up before con
guration is complete.
Operation of the device after pressing the
“
Esc
”
hotkey combination.
Switch-over between
“
OFF
”
and
“
Start
”
with the key shortcut for Escape ((Esc =
▼
+
▲
).
In menu group
Start
switch
Motor
to
“
ON
”
after setting.
Sequence
Setting
1
Menu language
If necessary, set the menu language in Menu group
“
Start
”
.
(Factory setting Englisch:
“
Language GB
”
)
2
Mode
Set the operating mode in the
“
Base setup
”
menu group (factory settings
1.01
=
Speed controllers
).
Attention!
When saving the operating mode, the respective preset factory operating-mode setting is loaded. That means,
the settings you have made, e.g., in
“
Motor setup
”
are lost. An exception: the menu language setting remains
preserved.
3
The settings in the
Motor setup
depend on the type of motor connected
3.1
Setting
Rated speed
(
F
fan
´
s nameplate).
3.2
Setting
Polecount
(
F
fan
´
s nameplate):
For 4-pole motors (type _ _ _ _ -
4
K _ - _ _ - _ _)
For 6-pole motors (type _ _ _ _ -
6
K _ - _ _ - _ _)
3.3
The correct
Rolling direction
depends on the type of fan. The
factory preset
is Rolling direction
1
. Find
the fan in the following table to determine the correct Rolling direction and to subsequently program.
Design Motor or fan
Type
Permissible Rolling
direction
MK - Motor
(direction of rotation when looking
at the rotor)
M
K
___.___.__._
left
right
MW - Motor
(direction of rotation when looking
at the cable)
M
W
___.___.__._
right
left
Centrifugal fan with single inlet
(direction of rotation when looking
at the suction side)
R___-__
K
.__._
R
/ _R___-__
K
.__._
R
right
R___-__
K
.__._
L
/ _R___-__
K
.__._
L
left
R___-__
N
.__._
A
/ _R___-__
N
.__._
A
left
R___-__
N
.__._
B
/ _R___-__
N
.__._
B
right
Operating Instruction
Econtrol
–
model series EXDM
Start-up
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
21/85