9.6.2
Settings for operation modes
6.01
Setting
Setting
Setpoint1
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 0.50 m/s
Setpoint2
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried
out: Display:
|
- - - - -
|
F
IO Setup).
Pband
Pband
small control range = short control times
big control range = longer control times and (higher controller stability)
Setting range: in measuring range of sensor
Factory setting: 0.50 m/s
Min. Speed
Minimal Speed
Setting range: 0...100 %
Factory setting: 0 %
Max. Speed
Maximal Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed
manual
”
Speed man.
Speed manual
Manual speed setting without in
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
F
IO
Setup).
Setting range: 0...100 %
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual
speed is indicated alternating with the actual value.
9.6.3
Menu for air velocity control
6.01
Parameter
Factory setting
User Setting
Start
Motor
OFF
(Menu dependent on device type available)
PIN input
- - - - -
Language
GB
Reset
OFF
Mode
6.01
Econtrol
1.14
SN:
xxx
Info
E1 Actual
0.45 m/s
E2 Actual
- - - -
Setpoint1
0.50 m/s
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB