Function Controller status
K1/ K2
1 = energized
0 = de-energized
Inverting
OFF
ON
1K
Operation without fault, line supply okay
1
0
2K
Fault with indication by relay
0
1
3K
Ext. Fault at digital input for external fault
1
0
4K
Over or falling below limits for modulation
1
0
5K
over or falling below limits for input signal
“
E1
”
1
0
6K
over or falling below limits for input signal
“
E2
”
1
0
7K
setpoint deviation to high
1
0
8K
Switching on second group
1
0
9.10.6
Programming Add-on module type Z-Modul-B
Program the additional inputs and outputs likewise in
“
IO Setup
”
.
After connecting the module, the settings menus are automatically expanded to include the additional
inputs and outputs.
•
1 x analog input 0 - 10 V. For mode
1.01
without function, starting from
2.01
funktion
|
1E
|
or
|
2E
|
possible.
–
Function
|
1E
|
for external target value function.
–
Function
|
2E
|
for external manual operation.
•
1 x output 0 - 10 V (A2 / GND), Function programmable, e.g., for: Fixed voltage, proportional
level control, proportional input signal, group control, drive 2.
•
3x digital inputs (D3 / GND, D4 / GND, D5 / GND) function programmable, e.g.: Enable (ON /
OFF), external malfunction, output limitation, input 1/2, target value 1/2, internal/external preset,
controller / manual operation, control-function reversal (
“
heating
”
/
“
cooling
”
).
•
2 x relay outputs (
“
K3
”
and
“
K4
”
) Function programmable, e.g., for: Status signals, alarm
indications, external malfunctions at the digital input, level-control threshold, input signal thresh-
old, offset threshold (deviation between current and target value), group control.
Parameter
Factory setting User Setting
=0RGXO%
42
44
41
32
34
31
A2 GND E3 GND D3
D4
D5 GND
OUT
0...10V
(I
max
=10mA)
+
IN
0...10V
(Ri>100k)
+
max. 5A/250VAC
Anal
og OUT
2
3
2
Analog IN
3
Di
gi
tal
IN
3
Di
git
a
l IN
4
Di
gi
tal
IN
5
K4
K3
16.05.2007
v_moea01k0.VSD
Programming of following functions of mode
2.03
is not
permissible on Z-Modul-B:
|
6A
|
,
|
7A
|
,
|
9K
|
,
|
10K
|
A2 Function
1A
A2 min.
0.0 V
A2 max.
10.0 V
A2 Inverting
OFF
D3 Function
OFF
D3 Inverting
- - - -
D4 Function
OFF
D4 Inverting
- - - -
D5 Function
OFF
D5 Inverting
- - - -
E3 Function
OFF
E3 Inverting
- - - -
K3 Function
OFF
K3 Inverting
- - - -
K4 Function
OFF
K4 Inverting
- - - -