9.5 Volume control
5.01
...
5.02
9.5.1
Basic setting
5.01
and
5.02
Setting
Base setup
Base setup
Mode
Mode selection e.g.
5.01
E1 Analog In
E1 Analog In
In all group operating modes 5 (
5.01
and
5.02
)
“
E1 Analog In
”
factory setting
“
DSG200.
”
Selection sensor measuring range:
“
DSG50
”
, *
“
DSG100
”
,
“
DSG200
”
, *
“
DSG300
”
,
“
DSG500
”
,
“
DSG1000
”
,
“
DSG2000
”
,
“
DSG4000
”
,
“
DSG6000
”
(* no standard type).
For sensors with 0 - 20 mA or 4 - 20 mA signal (
F
jumper for input signal),
select measuring range
“
DSG50
”
...
“
DSG6000
”
.
K Factor
K Factor
Input of the
“
K factor
”
dependent on the fan (inlet duct).
setting range: 0...7.000
Factory setting: 75
E1 Offset
E1 Offset
Sensor calibration with calibrated comparison device
E2 Function
E2 Function
(only for special applications)
•
External setpoint = Function
|
1E
|
by external signal (0 - 10 V) instead of
“
Setpoint1
”
. 0 - 10 V
≙
0 - 100 % setting range
•
External manual operation via external signal (0 - 10 V) = Function
|
2E
|
Switch over between settings on the device and external manual
operation via digital input (
F
IO Setup).
•
Measurement value = function
|
7E
|
e.g. for limit indication, display in Info
menu
“
E2 Actual
”
Modes
5.02
with two sensors
Modes with two sensors The function is automatically jointly programmed in
operating modes using 2 sensors. The second analog input is thus allocated
and additional function allocations are not possible. For
5.02
E2 Function at
|
6E
|
preprogrammed = sensor for setpoint lowering. Pre-programmed sensor
type
“
TF
”
.
9.5.2
Setting for operation modes
5.01
...
5.02
•
5.01
Volume control, Setpoint in m
3
/h
•
5.02
Volume control for ventilation systems setpoint depending on outdoor temperature.
Setting
Setting
Setpoint1
Setpoint1
Setpoint in m
3
/h (m
3
/s)
Setting range: depending on measuring range of sensor and
“
K factor
”
Factory setting: 530 m
3
/h
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
40/85