Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed
manual
”
Speed man.
Speed manual
Manual speed setting without in
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
F
IO
Setup).
Setting range: 0...100 %
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual
speed is indicated alternating with the actual value.
Additional menu item for mode
4.02
and
4.03
with outside-temperature dependent target-
setpoint.
Outside-temperature dependent target-setpoint
AT
P-min
-15 °C
T-min.
30 °C
T-Start
S1
09.05.2007
v_sollwert_aussentemp_abhaengig_pa.vsd
[Pa]
S2
S1 Setpoint1
S2Setpoint2
P-Min SA Minimum pressure
T-min Minimum temperature
T-Start Setpoint reducing will start below this outside temperature
AT Outdoor temperature
An outside temperature compensation can
be activated (sensor connection
“
E2
”
to
“
Analog In 2
”
) when being operated as a
pressure regulation device.
An optimal building climate, e.g., can be
achieved through this. Through this func-
tion, the set and active
“
Setpoint1
”
or
“
Set-
point2
”
is automatically changed propor-
tional to the measured outside temperature
(
F
Info:
“
Setpoint control
”
).
T-Band SA
T-Band SA
Temperature range in which the setpoint change continiously with outside
temperature
T-Start SA
T-Start SA
Setpoint reducing will start below this outside temperature
P-Min SA
P-Min SA
Minimum pressure for very low outside temperature
9.4.3
Menu for pressure control airconditioning
4.01
...
4.03
Parameter
Factory setting
User Setting
Start
Motor
OFF
OFF
OFF
(Menu dependent on device type available)
PIN input
- - - - -
- - - - -
- - - - -
Language
G
B
G
B
G
B
Reset
OFF
OFF
OFF
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
38/85