of connecting multiple SDI-12 sensors. Standard SDI-12 sensors have a minimum of three
wires: +12V, Data, and Gnd.
The SDI-12 Sensor Input allows the System 5000
to communicate with and retrieve
TM
measurement parameters from a standard SDI-12 sensor. The options on the screen combine to
retrieve the requested data. For example, in the above screen, a command of “0M” would first be
sent, the reply would be received and parsed, the necessary time would be delayed and then the
data values would be retrieved. In this case, the first sdi-12 parameter would be recorded. Due
to the possible long length of time needed for SDI-12 Measurements, the SDI-12 Value can be
manually retrieved via the Test button and does not continuously retrieve the data. Once a Test
has been started the measurement can be aborted by pressing the Abort button, which is shown
once the Test has begun.
Sensor Address:
Defines the sensor address to query. Addresses can be any single digit number
or letter. Sensor addresses are case-sensitive, thus sensor H is different from sensor h. Most
sensors typically use a number for their address. Finding unknown sensor addresses as well as
changing current addresses can be done within the SDI-12 Transparent Mode.
Measurement CMD:
Defines the measurement command to use when querying the SDI-12
Sensor. Available commands are M, R, C, MC, RC, CC, and D with an optional number
specified after the command (e.g. M1, MC2, etc).
SDI-12 Parameter:
Defines the parameter to record after receiving the measurement data. A
value of 5, for example, will return the fifth value received from the Data command after a
standard Measure command. All necessary waiting and available parameters will be interpreted
and received by the System 5000 .
TM
Transparent Mode:
The built-in SDI-12 Transparent Mode, discussed more in Chapter 11,
allows all SDI-12 communication (to/from the System 5000
as well as from other sensors on
TM
the sdi-12 line) to be seen. Pre-defined as well as custom/extended SDI-12 commands can be
issued from within the Transparent Mode.
5-12 Inputs
System 5000
TM
Summary of Contents for WaterLog Series
Page 1: ...Model System 5000TM Owner s Manual Revision 1 4 2...
Page 2: ......
Page 8: ......
Page 24: ...2 10 Hardware Overview System 5000TM...
Page 58: ...5 14 Inputs System 5000TM...
Page 128: ...10 14 System Setup General Setup System 5000TM...
Page 144: ...12 6 System Setup Inputs Outputs System 5000TM...
Page 168: ...14 4 Maintenance and Troubleshooting System 5000TM...
Page 170: ...A 2 System 5000 Specifications System 5000TM...
Page 172: ...B 2 Pressure Sensor Option Module Specifications System 5000TM...
Page 174: ...C 2 Analog Digital Option Module Specifications System 5000TM...