SECTION 2 – OPTIVIEW CONTROL CENTER
Current Limit Setpoint.
Chiller Pulldown Demand Limit
Access Level Required:
OPERATOR
Allows the user to specify the maximum allowed Chill-
er Current during the Chiller Pulldown Period. The
Chiller Pulldown Period is in effect from the instant the
chiller enters “System Run” until the Leaving Chilled
liquid temperature is within 2º F of the Leaving Chilled
Liquid Temperature Setpoint. Refer to the Electro-me-
chanical Starter Screen for a detailed explanation of the
Chiller Pulldown Demand Current Setpoint.
Access Level Required:
VIEW
Generates Setpoints print report.
Navigation
Home
Access Level Required:
VIEW
Causes an instant return to the Home Screen.
Setup
Access Level Required:
VIEW
Moves to the sub-screen allowing setup of general sys-
tem parameters.