SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.69-O1
ISSUE DATE: 9/30/2012
2
Hot Gas Bypass Control Mode
Indicates whether the Hot Gas Bypass is under automat-
ic, manual or override control. “Override” is displayed
during Minimum Load override conditions or when the
Compressor Motor Variable Speed (if equipped) Drive
is running at less than maximum speed.
Programmable
Close Percentage
Service technicians refer to YORK Service Manual
160.69-M1.
Hold Period
Service technicians refer to YORK Service Manual
160.69-M1.
Surge Sensitivity
Service technicians refer to YORK Service Manual
160.69-M1.
Minimum Load
Service technicians refer to YORK Service Manual
160.69-M1.
Maximum Open
Service Technicians refer to YORK Service Manual
160.69-M1.
[Hot Gas Bypass Control] Open (Manual)
This key puts the Hot Gas Bypass Control in manual
mode and increases the valve position by 5%.
[Hot Gas Bypass Control] Close (Manual)
This key puts the Hot Gas Bypass Control in manual
mode and decreases the valve position by 5%.
[Hot Gas Bypass Control] Auto
Returns the Hot Gas Bypass Control to automatic
mode.
Navigation
Home
Causes an instant return to the Home Screen
Compressor
Causes an instant return to the Compressor Screen