SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.69-O1
ISSUE DATE: 9/30/2012
2
Refrigerant Level Position
Displays the present position of the refrigerant level if
this function is enabled.
Refrigerant Level Setpoint
Displays the setpoint to which the refrigerant level is
being controlled.
Ramp Up Time Remaining
Displays the time remaining in the period in which the
Refrigerant Level setpoint is being ramped to a Refrig-
erant Level target setpoint. This is only displayed if the
Refrigerant Ramp is enabled and the value is nonzero.
Service Technicians refer to YORK Service Manual
160.69-M1.
Programmable
High Pressure Warning Threshold
Access Level Required:
SERVICE
This value allows the user to define the condenser pres-
sure at which the chiller will initiate a warning.
Drop Leg (Enabled / Disabled)
Access Level Required:
SERVICE
When a Drop Leg Refrigerant Sensor has been installed
it must be enabled via this toggle before the system will
utilize the new, enhanced resolution input. Service Tech-
nicians refer to YORK Service Manual 160.69-M1.
Navigation
Home
Access Level Required:
VIEW
Causes an instant return to the Home Screen.
Refrigerant Level Control
Access Level Required:
SERVICE
Moves to the sub-screen allowing programming of the
refrigerant liquid level control setpoints.