JOHNSON CONTROLS
36
FORM 160.69-O1
ISSUE DATE: 9/30/2012
SECTION 2 – OPTIVIEW CONTROL CENTER
Leaving Chilled Liquid Temperature Setpoints –
Restart
Displays the Leaving Chilled Liquid Temperature at
which the chiller will restart after it has shut down due to
over-cooling temperature. By default, the chiller will re-
start at the Leaving Chilled Liquid Temperature Setpoint.
Programmable
Local Leaving Chilled Liquid Temperature - Range
Access Level Required:
OPERATOR
This is the range over which an analog (0-20mA,
4-20mA, 0-10VDC or 2-10VDC) in Analog Remote
Mode or a digital signal (PWM) in Digital remote
mode can reset the Leaving Chilled Liquid Tempera-
ture setpoint above the operator programmed Base
Setpoint (see below). Programmable as either 10°F or
20°F, with a default of 20°F, it is added to the Base
value to create a range over which the remote device
can reset the setpoint. For example, if this setpoint is
programmed for 10°F and the operator programmed
value is 45°F, then the remote device can set the Leav-
ing Chilled Liquid Temperature setpoint over the range
45.0° - 55.0°F.
Local Leaving Chilled Liquid Temperature - Set-
point
Access Level Required:
OPERATOR
This value allows the user to define the Leaving
Chilled Liquid Temperature that is to be maintained by
the chiller. It is programmable over the range of 38.0°F
to 70.0°F (water) or 10.0°F to 70.0°F (brine). If Smart
Freeze (see below) is enabled, the range is 36.0°F to
70.0°F (water). A remote device can provide an ana-
log signal (0-20mA, 4-20mA, 0-10VDC or 2-10VDC)
in Analog Remote mode, or PWM signal in Digital
Remote mode that changes the setpoint by creating
an offset above the operator programmed Base Leav-
ing Chilled Liquid Temperature setpoint. This offset
may be defined up to 10.0°F or 20.0°F above the Base
setpoint (see the Remote Leaving Chilled Liquid Tem-
perature Setpoint Range description above). Addition-
ally, MicroGateway (in ISN Remote mode) can define
the setpoint through a serial data stream. In this case,
the incoming setpoint is not an offset that is applied to
the locally programmed Base setpoint value, but rather
is the setpoint value itself.
Leaving Chilled Liquid Temperature Cycling Off-
set - Shutdown
Access Level Required:
OPERATOR
This value allows the user to specify the Leaving
Chilled Liquid Temperature at which the chiller will
shut down on a
LEAVING CHILLED LIQUID –
LOW TEMPERATURE
cycling shutdown. This is
done by defining an offset below the Leaving Chilled
Liquid Temperature setpoint. It is programmable over
a range of 1°F to 64°F below the setpoint, to a mini-
mum cutout of 36°F (water), 34°F (water with Smart
Freeze enabled) or 6°F (brine). It establishes the mini-
mum allowable temperature for the Leaving Chilled
Liquid Temperature and prevents over-cooling of the
building. Anytime the Leaving Chilled Liquid Tem-
perature setpoint is increased, the shutdown threshold
is 36.0°F (water) or 6.0°F (brine) for the next ten (10)
minutes. If Smart Freeze (see below) is enabled, the
threshold is 34.0°F for the next 10 minutes. After ten
(10) minutes have elapsed, the shutdown threshold be-
comes the programmed setpoint value.
Leaving Chilled Liquid Temperature Cycling
Offset - Restart
Access Level Required:
OPERATOR
This value allows the user to specify the Leaving
Chilled Liquid Temperature at which the chiller will
restart after a shutdown on a
LEAVING CHILLED
LIQUID – LOW TEMPERATURE
cycling shut-
down. This is done by defining an offset above the
Leaving Chilled Liquid Temperature setpoint. It is
programmable over a range of 0°F to 70°F above the
setpoint, to a maximum restart value of 80°F. The
chiller will automatically restart when this temperature
is reached. This setpoint can be used to reduce chiller
cycling by delaying the chiller restart until the cooling
load has increased.
Brine Low Evaporator Cutout
Access Level Required:
SERVICE
This value is only available in Brine mode. It allows
the user to specify the Evaporator Pressure at which a
safety shutdown is initiated. Service Technicians refer
to YORK Service Manual 160.69-M1.