Appendix
App-13
IM 767361-01E
RS-232 (Response to the <ESC>S Command)
DI08
DI07
DI06
DI05
DI04
DI03
DI02
DI01
0
(fixed)
1
(fixed)
ERROR
OVER
Syntax
Error
24 VOUT
-OL-
Calcula-
tion
END
Auto
store
END
For DIO1 to DIO6, the status byte format is identical to that used for the GP-IB
interface. For details, refer to page App-12.
Note
• After the status byte responds to the serial poll from the controller, this bit is reset to 0. Until
the serial poll is responded to, each interrupt is stored, and if more interrupts occur thereafter,
they are added.
• To prevent the status byte being affected by a computation END, syntax ERROR, or OVER,
use the “IM” command to set a value with the corresponding bits set to 0.
Data Output Format
Output Format for Measurement and Computation Data (Response to the “OD” Command)
Data Format
Each data consists of a 4-byte header and 8 bytes of data.
You can specify whether a header is output using the H command.
Header
Data
Header Section
The header section consists of four bytes (h1 to h4). indicates a space.
h1 h2 h3 h4
h1 to h3:
Data type h4:
Data state
KPA: Pressure (kPa)
N: Normal measured data
KGF: Pressure (kgf/cm
2
)
I: Overrange data
MHO: Pressure (mmH
2
0)
O: Computation overflow
MHG: Pressure (mmHg)
E: No data
IHO: Pressure (inH
2
0)
IHG: Pressure (inHg)
PSI: Pressure (psi)
PP
: Pressure %
DMM Header (MT220 Only)
h1 to h3: Data type
h4: Data state
V : DC voltage (V)
N: Normal measured data
A : DC current (mA)
I: Overrange data
PV
: DC voltage %
O: Computation overflow
PA
: DC current %
F: No DMM data when DMM function is off
ERR: Error %
E: No data
Appendix