52
Press
Menu
Press Digit
Select Key
Press Value Select
Key
dSPyno
Display #
____
0
1
PEAK key action
0
Display Peak
1
Display Valley
2
Peak (1
st
push), Valley (2
nd
push)
____0
1
Item to display
after Meter Reset
1
Item #1* (Quadrature Rate = Rate A - Rate B)
2
Item #2* (Rate A)
3
Item #3* (Rate B)
GAtE
_
t
Gate time*
_
0
00.00 _0
0
0.00 _00
0
.00
_000.
0
0 _000.0
0
Select digit to flash.
Select
0
thru
9
for flashing digit to set gate time* in
seconds. Decimal point location is fixed for 10 ms
resolution.
.
ti_Out
.
Time-out*
_
0
00.00 _0
0
0.00 _00
0
.00
_000.
0
0 _000.0
0
Select digit to flash.
Select
0
thru
9
for flashing digit to set time-out* in
seconds. Decimal point location is fixed for 10 ms
resolution.
FiLtEr
Filtering
_
0
0000
Signal filtering
0
Adaptive moving average filter. Restarts filter for
high actual changes in signal.
1
Conventional moving average filter without reset.
_0
0
000
Peak & Valley filtering
0
Peak* or Valley* value from unfiltered signal.
1
Peak* or Valley* value from filtered signal.
_00
0
00
Display filtering
0
Display value of unfiltered signal.
1
Display value of filtered signal.
_000
0
0
Adaptive filter setup
0
Set adaptive filter for normal noise.
1
Set adaptive filter for presence of high transients.
_0000
0
Filter time constant
0
No filter
1
0.1 sec
2
0.2 sec
3
0.4 sec
4
0.8 sec
5
1.6 sec
6
3.2 sec
7
6.4 sec
dEC.Pt1
Decimal pt1
1
.
11111
Decimal point flashes.
1
.
11111
11
.
1111
111
.
111
1111
.
11
11111
.
1
111111
.
Press to shift decimal point of reading.
dEC.Pt22
Decimal pt2
2
.
22222
Decimal point flashes.
Make the same as
dEC.Pt1
Scale and Offset scaling method if selected under
SEtuP
SCALE1
Scale
Factor 1
0
.00000 0.
0
0000 0.0
0
000
0.00
0
00 0.000
0
0 0.0000
0
Select the digit to flash
for the Scale Value, then
press one more time
for the Scale Multiplier.
Select
-9
thru
9
for flashing first digit and
0
thru
9
for
other flashing digits. This will set the Scale Value*
from -9.99999 to 9.99999 with a fixed decimal point.
Then press to select a value from
0.00001
to
100000
in decade steps for the Scale Multiplier.
Scale Factor = Scale Value x Scale Multiplier.
OFFSt1
.
Offset 1
0
00000 0
0
0000 00
0
000
000
0
00 0000
0
0 00000
0
Select digit to flash.
Select
-9
thru
9
for flashing first digit and
0
thru
9
for
other flashing digits. Use
dEC.Pt1
to set the decimal
point.
SCALE2
Scale Factor 2
Make the same as
SCALE1
.
OFFSt2
.
Offset 2
Make the same as
OFFSt1
.
Summary of Contents for 800 plus
Page 63: ...63 SERIAL CONNECTION EXAMPLES ...