16.1 List of Parameters
16.1.2 List of Parameters
16-26
Pn516
(2516 hex)
2
Input Signal Selections
7
0000 hex to
FFFF hex
–
8888
hex
All
After
restart
Setup
–
Pn51B
(251B hex)
4
Motor-Load Position
Deviation Overflow
Detection Level
0 to
1,073,741,823
1 refer-
ence
unit
1000
Rotary
Immedi-
ately
Setup
Pn51E
(251E hex)
2
Position Deviation Over-
flow Warning Level
10 to 100
1%
100
All
Immedi-
ately
Setup
Pn520
(2520 hex)
4
Position Deviation Over-
flow Alarm Level
1 to
1,073,741,823
1 refer-
ence
unit
5242880
All
Immedi-
ately
Setup
8-8,
Pn522
(2522 hex)
4
Positioning Completed
Width
0 to
1,073,741,824
1 refer-
ence
unit
7
All
Immedi-
ately
Setup
Pn524
(2524 hex)
4
Near Signal Width
1 to
1,073,741,824
1 refer-
ence
unit
1073741824
All
Immedi-
ately
Setup
Pn526
(2526 hex)
4
Position Deviation Over-
flow Alarm Level at
Servo ON
1 to
1,073,741,823
1 refer-
ence
unit
5242880
All
Immedi-
ately
Setup
Pn528
(2528 hex)
2
Position Deviation Over-
flow Warning Level at
Servo ON
10 to 100
1%
100
All
Immedi-
ately
Setup
Pn529
(2529 hex)
2
Speed Limit Level at
Servo ON
0 to 10,000
1 min
-1
10000
Rotary
Immedi-
ately
Setup
Pn52A
(252A hex)
2
Multiplier per Fully-
closed Rotation
0 to 100
1%
20
Rotary
Immedi-
ately
Tuning
Pn52B
(252B hex)
2
Overload Warning Level
1 to 100
1%
20
All
Immedi-
ately
Setup
Pn52C
(252C hex)
2
Base Current Derating
at Motor Overload
Detection
10 to 100
1%
100
All
After
restart
Setup
Continued on next page.
Continued from previous page.
Parameter
No.
Size
Name
Setting
Range
Setting
Unit
Default
Setting
Applicable
Motors
When
Enabled
Classi-
fication
Refer-
ence
n.
X
FSTP (Forced Stop Input) Signal Allocation
Reference
0
Enable drive when CN1-13 input signal is ON (closed).
1
Enable drive when CN1-7 input signal is ON (closed).
2
Enable drive when CN1-8 input signal is ON (closed).
3
Enable drive when CN1-9 input signal is ON (closed).
4
Enable drive when CN1-10 input signal is ON (closed).
5
Enable drive when CN1-11 input signal is ON (closed).
6
Enable drive when CN1-12 input signal is ON (closed).
7
Set the signal to always prohibit drive (always force the motor to
stop).
8
Set the signal to always enable drive (always disable forcing the
motor to stop).
9
Enable drive when CN1-13 input signal is OFF (open).
A
Enable drive when CN1-7 input signal is OFF (open).
B
Enable drive when CN1-8 input signal is OFF (open).
C
Enable drive when CN1-9 input signal is OFF (open).
D
Enable drive when CN1-10 input signal is OFF (open).
E
Enable drive when CN1-11 input signal is OFF (open).
F
Enable drive when CN1-12 input signal is OFF (open).
n.
X
Reserved parameter (Do not change.)
n.
X
Reserved parameter (Do not change.)
n.X
Reserved parameter (Do not change.)