2.2 Basic Module
2.2.4 218IFA Module (Ethernet)
2-22
Automatic Receive Setting Screen for Message Communication
The automatic receive function can be enabled only for connections where the connection number = 1.
The automatic receive function enables you to automatically run a function equivalent to the MSG-RCV function.
The following table explains each setting item.
Item
Setting Range
Details
Default
Automatic Recep-
tion Enable/Disable
Enable/Disable
Select whether to enable automatic reception.
Note: When the local port number is not yet set, it becomes invalid
regardless of the enable/disable selection.
Enable
The setting items below can only be set when the Automatic Reception is set to “Enable.”
Transmission Buffer
Channel
Cannot be set
(fixed at one)
The communication buffer channel is usually used for data
exchanged between the MSG-SND/MSG-RCV function and
218IFA.
The communication buffer channel is associated with the connec-
tion according to the input item “CH-NO” for the MSG-SND/
MSG-RCV function and node connection number (PARAM02)
setting for the parameter list (PARAM).
When automatic reception is running, the function equivalent to
the MSG-RCV function is realized by using the communication
buffer channel number “1.”
1
Readout of Input
Relay
IW0000 to
IWFFFF
Set a start register of the input relay used for the automatic recep-
tion.
IW0000
Readout of Input
Register
IW0000 to
IWFFFF
Set a start register of the input register used for the automatic
reception.
IW0000
Readout/Write-in of
Coil
MW00000 to
MW65534
Set a start read/write register of the coil used for the automatic
reception.
MW00000
Readout/Write-in of
Hold Register
MW00000 to
MW65534
Set a start read/write register of the holding register used for auto-
matic reception.
MW00000
Write-in Width of
Coil/Hold Register
(LO)
MW00000 to
MW65534
Set a write range (LO) of the coil/holding registers used for auto-
matic reception.
MW00000
Write-in Width of
Coil/Hold Register
(HI)
MW00000 to
MW65534
Set a write range (HI) of the coil/holding registers used for the
automatic reception.
MW65534
Summary of Contents for JEPMC-MP2300S-E
Page 14: ...MEMO ...
Page 24: ...MEMO ...
Page 114: ...MEMO ...
Page 132: ...MEMO ...
Page 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Page 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Page 190: ...MEMO ...
Page 280: ...MEMO ...
Page 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Page 310: ...MEMO ...