![YASKAWA JEPMC-MP2300S-E User Manual Download Page 173](http://html.mh-extra.com/html/yaskawa/jepmc-mp2300s-e/jepmc-mp2300s-e_user-manual_907071173.webp)
5.3 Registers
5.3.4 Register Designation
5-41
5
Outline of Motion Control Systems
5.3.4 Register Designation
Registers can be specified directly by register number or by symbol (register name). A combination of both of these
register designation methods can be used in ladder programs.
When using the symbol specification method, the relationship between symbols and register numbers must be defined.
The following table shows the register specification methods.
Designation
Method
Designation Example for Each Data Type
Register
Number
Direct
Designation
Bit register:
MB00100AX
Integer register:
MW00100X
Double-length integer register:
ML00100X
Real number register:
MF00100X
Address register:
MA00100X
X: When specifying subscripts, subscript i or j is added after the register number.
Symbol
Designation
Bit register:
RESET1-A.X
Integer register:
STIME-H.X
Double-length integer registers:
POS-REF.X
Real number registers:
IN-DEF.X
Address registers:
PID-DATA.X
↓
8 alphanumeric characters max.
X: When specifying subscripts, a period (.) is added after the symbol (8 alphanu-
meric characters max.) and then a subscript i or j is added.
T
V
Direct Designation
Register Number
Register No.:
No.
Bit No.
Subscript
Subscript i or j can be specified
When T = B (bit register) (hexadecimal: 0
to F)
Register number allocated for V
(decimal/hexadecimal)
Register type
(DWG: S, M, I, O, C, #, or D)
(Function: S, M, I, O, C, #, D,
X
, Y,
Z
, or A)
Data type allocated by V (B, W, L, F, or A)
X
X X X X X X X
Symbol:
Symbol name
Subscript
Subscript i or j can be specified
Required if using subscripts
Alphanumeric characters or symbols
English characters or symbols
(Symbol names cannot start with numerals.)
Name for registers: 8 characters max.
Symbol
Designation
Summary of Contents for JEPMC-MP2300S-E
Page 14: ...MEMO ...
Page 24: ...MEMO ...
Page 114: ...MEMO ...
Page 132: ...MEMO ...
Page 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Page 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Page 190: ...MEMO ...
Page 280: ...MEMO ...
Page 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Page 310: ...MEMO ...