![YASKAWA JEPMC-MP2300S-E User Manual Download Page 452](http://html.mh-extra.com/html/yaskawa/jepmc-mp2300s-e/jepmc-mp2300s-e_user-manual_907071452.webp)
A-98
G.2.8 Relationship between Data Address, Data Size, and Offset for MSG-RCV
Function
The relationships between data address, data size, and offset when received with offset are as follows:
( 1 ) When Reading
Start address of
the read data
Start address of
the read data
MW00000
IW
Data address B
Offset A
Data si
z
e C
Data
M register
MP2
00 series (reception: slave)
IW00000
IW
Data address B
Offset A
Data si
z
e C
Data
I register
Remote device (transmission: master)
Data si
z
e C
Data
Data flow when reading
Parameter list
PARAM00
PARAM01
:
PARAM08
PARAM09
PARAM10
PARAM11
PARAM12
PARAM13
:
PARAM16
Offset A
Write range
♦
Transmission side sets the data address B and the data si
z
e C.
♦
In case of non-procedure, read cannot be received.
♦
The valid offset parameter may differ according to each data type.
♦
The data type and register correspond as follows:
Coil: MB
, holding register: MW
Input relay: lB
, input register: IW
[MSG-RCV function] Parameter list
Summary of Contents for JEPMC-MP2300S-E
Page 14: ...MEMO ...
Page 24: ...MEMO ...
Page 114: ...MEMO ...
Page 132: ...MEMO ...
Page 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Page 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Page 190: ...MEMO ...
Page 280: ...MEMO ...
Page 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Page 310: ...MEMO ...