![YASKAWA JEPMC-MP2300S-E User Manual Download Page 214](http://html.mh-extra.com/html/yaskawa/jepmc-mp2300s-e/jepmc-mp2300s-e_user-manual_907071214.webp)
6.2 Communication with Other MP Series
6.2.2 When the MP2300S Acts as a Slave (ladder program which uses a MSG-RCV function)
6-24
Parameter list setting example for message receive function
An example of a parameter list setting when receiving messages from a transmit source using the connection with
a connection number = 2 follows:
Note: IN: Input, OUT: Output, SYS: For system use
Table 6.5 Parameter List Setting Example (parameter list start address Param=DA00000)
Register
Number
Setting
Value
Parameter
Number
IN/OUT
Remarks
DW00000
-
PARAM00
OUT
Process result
DW00001
-
PARAM01
OUT
Status
DW00002
00002
PARAM02
IN
Connection number = 2
DW00003
-
PARAM03
OUT
Option
DW00004
-
PARAM04
OUT
Function code
DW00005
-
PARAM05
OUT
Data address
DW00006
-
PARAM06
OUT
Data size
DW00007
-
PARAM07
OUT
Remote CPU number
DW00008
00000
PARAM08
IN
Coil offset = 0 word
DW00009
00000
PARAM09
IN
Input relay offset = 0 word
DW00010
00000
PARAM10
IN
Input register offset = 0 word
DW00011
00000
PARAM11
IN
Holding register offset = 0 word
DW00012
00000
PARAM12
IN
Writable address lower limit = MW00000
DW00013
65534
PARAM13
IN
Writable address upper limit = MW65534
DW00014
-
PARAM14
SYS
Reserved by the system. (Zero clear at startup)
DW00015
-
PARAM15
SYS
Reserved by the system.
DW00016
-
PARAM16
SYS
Reserved by the system.
Summary of Contents for JEPMC-MP2300S-E
Page 14: ...MEMO ...
Page 24: ...MEMO ...
Page 114: ...MEMO ...
Page 132: ...MEMO ...
Page 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Page 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Page 190: ...MEMO ...
Page 280: ...MEMO ...
Page 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Page 310: ...MEMO ...