5.5 Precaution on Using MP2300S
5.5.3 Setting and Changing the Scan Time
5-57
5
Outline of Motion Control Systems
( 2 ) Scan Time Set Value Examples
0.8-ms Maximum Scan Time and 1-ms Communication Cycle (MECHATROLINK-II Only)
High-speed (or low-speed) scan set value
≥
1.25
×
0.8 (
=
1 ms)
High-speed (or low-speed) scan set value
=
1 ms, 2 ms, 3 ms, etc. (an integral multiple of at least 1 ms)
1.4-ms Maximum Scan Time and 1-ms Communication Cycle (MECHATROLINK-II Only)
High-speed (or low-speed) scan set value
≥
1.25
×
1.4 (
=
1.75 ms)
High-speed (or low-speed) scan set value
=
2 ms, 3 ms, etc. (an integral multiple of at least 2 ms)
0.8-ms Maximum Scan Time and 2-ms Communication Cycle (MECHATROLINK-I or MECHA-
TROLINK-II)
High-speed (or low-speed) scan set value
≥
1.25
×
0.8 (
=
1 ms)
High-speed (or low-speed) scan set value
=
1 ms, 2 ms, 4 ms, etc. (an integral multiple of 2 ms at 1 ms and 2 ms or
higher)
1.4-ms Maximum Scan Time and 2-ms Communication Cycle (MECHATROLINK-I or MECHA-
TROLINK-II)
High-speed (or low-speed) scan set value
≥
1.25
×
1.4 (
=
1.75 ms)
High-speed (or low-speed) scan set value
=
2 ms, 4 ms, etc. (an integral multiple of 2 ms at 2 ms or higher)
Summary of Contents for JEPMC-MP2300S-E
Page 14: ...MEMO ...
Page 24: ...MEMO ...
Page 114: ...MEMO ...
Page 132: ...MEMO ...
Page 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Page 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Page 190: ...MEMO ...
Page 280: ...MEMO ...
Page 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Page 310: ...MEMO ...