User Constant Tables
5-
31
H3-14
Gain (terminal AI4)
Sets the input gain (level) when
terminal AI3 is 10 V. Set
according to the 100% value
selected in H3-13.
0.0 to
1000.0
100.0%
Yes
A
A
45DH
Term AI4 Gain
H3-15
Bias (terminal AI4)
Sets the input gain (level) when
terminal AI3 is 0 V. Set accord-
ing to the 100% value selected
in H3-13.
-100.0
to
100.0
0.0%
Yes
A
A
45EH
Term AI4 Bias
H3-16
Analog input filter
time constant
Sets primary delay filter time
constant in seconds for the four
analog input terminal
(AI1,AI2,AI3,AI4).
Effective for noise control etc.
0.00 to
2.00
0.00
s
No
A
A
45FH
Filter Avg Time
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display