6
-52
H4-08
Gain (terminal AO3)
Sets the multi-function analog
output 3 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
0 to
30.00
1.00
Yes
A
A
477H
Term AO3 Gain
H4-09
Bias (terminal AO3)
Sets the multi-function analog
output 3 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
-100.0
to
100.0
0.0%
Yes
A
A
478H
Term AO3 Bias
H4-10
Monitor selection
(terminal AO4)
Sets the number of the monitor
item to be output (U1-
)
from terminal A04.
0 to 99
9
Yes
A
A
479H
Term AO4 Signal
H4-11
Gain (terminal AO4)
Sets the multi-function analog
output 4 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
0 to
30.00
1.00
Yes
A
A
47AH
Term AO4 Gain
H4-12
Bias (terminal AO4)
Sets the multi-function analog
output 4 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
-100.0
to
100.0
0.0%
Yes
A
A
47BH
Term AO4 Bias
H4-13
Analog output signal
level selection
0: 0 to +10 V
1: -10 to +10 V
0 or 1
1
No
A
A
47CH
Signal Select
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display