User Constant Tables
5-
23
* 1. The factory settings depend on the Inverter capacity.
* 2. Only multiples of 2 can be set.
E2-11
Motor rated output
Set the rated output of the
motor in units of 0.01 kW.
This constant is automatically
set during autotuning.
0 to
10000
630
kW
No
Q
Q
36AH
Mtr Rated Power
E2-12
Motor wiring resistor
Set the motor wiring resistance
in % units.
0.00 to
1.00
0.00%
Yes
A
A
36BH
Wiring Resistor
E2-13
Motor temperature OH
level
Set the motor temperature OH
level in
°
C units.
50 to
200
120
°
C
No
A
A
36CH
Motor Temp OHLVL
E2-14
Motor Thermistor
selection
0: Motor Thermistor disabled.
1: Motor Thermistor enabled.
0 or 1
0
No
A
A
36DH
Motor Thermistor
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display