![YASKAWA FSDrive-MV1S Instructions Manual Download Page 170](http://html1.mh-extra.com/html/yaskawa/fsdrive-mv1s/fsdrive-mv1s_instructions-manual_3478741170.webp)
6
-46
Time Chart
The time chart when using the UP/DOWN command is shown below.
Fig 6.22 UP/DOWN Commands Time Chart
Jog Frequency Operation without Forward and Reverse Commands
(FJOG/RJOG)
The FJOG/RJOG command functions operate the Inverter using jog frequencies by using the terminal on/off
operation. When using the FJOG/RJOG commands, there is no need to input the Run Command.
To use this function, set one of the constants H1-03 to H1-16 (multi-function contact input terminal S3 to S16
function selection) to 12 (FJOG command) or 13 (RJOG command).
Related Constants
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
d1-17
Jog frequency
reference
The frequency reference when
the jog frequency reference
selection, FJOG command, or
RJOG command is on.
0.00 to
100.00
10.00%
Yes
Q
Q
2D0H
Jog Reference
Output frequency
Accelerates to
lower limit
Same
frequency
Reference
frequency reset
* The frequency matching signal turns on when the motor is not accelerating/
decelerating while the Run Command is on.
Lower limit
Forward operation/stop
UP command
DOWN command
Frequency
matching signal*
Power supply
Upper limit
On
On
On
On
On
On