5
-18
Reference Constants: d
The following settings are made with the reference constants (d constants): Frequency references.
Preset Reference: d1
User constants for frequency references are shown in the following table.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
d1-01
Frequency reference 1 Sets the frequency reference in
the units used in o1-03.
0.00 to
100.00
0.00%
Yes
Q
Q
2C0H
Reference 1
d1-02
Frequency reference 2 The frequency reference when
multi-step speed reference 1 is
on for a multi-function input.
0.00 to
110.00
0.00%
Yes
Q
Q
2C1H
Reference 2
d1-03
Frequency reference 3 The frequency reference when
multi-step speed reference 2 is
on for a multi-function input.
0.00 to
110.00
0.00%
Yes
Q
Q
2C2H
Reference 3
d1-04
Frequency reference 4 The frequency reference when
multi-step speed references 1
and 2 are on for multi-function
inputs.
0.00 to
110.00
0.00%
Yes
Q
Q
2C3H
Reference 4
d1-05
Frequency reference 5 The frequency when multi-step
speed reference 3 is on for a
multi-function input.
0.00 to
110.00
0.00%
Yes
Q
Q
2C4H
Reference 5
d1-06
Frequency reference 6 The frequency reference when
multi-step speed references 1
and 3 are on for multi-function
inputs.
0.00 to
110.00
0.00%
Yes
Q
Q
2C5H
Reference 6
d1-07
Frequency reference 7 The frequency reference when
multi-step speed references 2
and 3 are on for multi-function
inputs.
0.00 to
110.00
0.00%
Yes
Q
Q
2C6H
Reference 7
d1-08
Frequency reference 8 The frequency reference when
multi-step speed references 1,
2, and 3 are on for multi-func-
tion inputs.
0.00 to
110.00
0.00%
Yes
Q
Q
2C7H
Reference 8
d1-17
Jog frequency
reference
The frequency reference when
the jog frequency reference
selection, FJOG command, or
RJOG command is on.
0.00 to
100.00
10.00%
Yes
Q
Q
2D0H
Jog Reference