Digital Operator Functions
This section explains the Digital Operator functions.
Setting Digital Operator Functions
You can set Digital Operator-related constants such as selecting the Digital Operator display, multi-function
selections, and copy functions.
Related Constants
Disabling the STOP Key
If b1-02 (Operation Method Selection) is set to 1, 2, or 3, the Stop Command from the STOP Key on the Dig-
ital Operator is an emergency Stop Command.
Set o2-02 to 0 to disable emergency Stop Commands from the STOP Key on the Digital Operator.
Disabling the LOCAL/REMOTE Key
Set o2-01 to 0 to disable the LOCAL/REMOTE Key on the Digital Operator. You cannot switch Inverter ref-
erence inputs set using reference inputs from the Digital Operator, b1-01 (Reference Selection), or b1-02
(Operation Method Selection).
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
o2-01
LOCAL/REMOTE
key enable/disable
Sets the Digital Operator Local/
Remote Key
0: Disabled
1: Enabled (Switches between the
Digital Operator and the
constant settings.)
0 or 1
1
No
A
A
6F0H
Local/Remote Key
o2-02
STOP key during
control circuit ter-
minal operation
Sets the Stop Key in the run mode.
0: Disabled (When the Run Com-
mand is issued from and
external terminal, the Stop Key
is disabled.)
1: Enabled (Effective even during
run.)
0 or 1
0
No
A
A
6F1H
Oper STOP Key
o2-05
Frequency
reference setting
method selection
When the frequency reference is
set on the Digital Operator fre-
quency reference monitor, sets
whether the Enter Key is necessary.
0: Enter Key needed
1: Enter Key not needed
When set to 1, the Inverter accepts
the frequency reference without
Enter Key operation.
0 or 1
0
No
A
A
6F4H
Operator M.O.P.
o2-07
Cumulative opera-
tion time setting
Sets the cumulative operation time
in hour units.
Operation time is calculated from
the set values.
0 to
65535
0 hr
No
A
A
6F6H
Elapsed Time Set