6
-16
Operation Avoiding Resonance (Jump Frequency Function)
The jump frequency function operates the motor while avoiding resonance caused by characteristic frequen-
cies in the machinery.
This function is effective in creating a frequency reference dead band.
During constant-speed operation, operation within the jump frequency range is prohibited. Smooth operation
still used during acceleration and deceleration, i.e., jumps are not performed.
Related Constants
The relationship between the output frequency and the jump frequency reference is as follows:
H3-12
Signal level selection
(terminal AI4)
0: 0 to 10V
1: -10V to 10V
0 or 1
0
No
A
A
45BH
Term AI4 Signal
H3-13
Multi-function analog
input
(terminal AI4)
Select multi-function analog
input function for terminal AI4.
00 to
1FH
0FH
No
A
A
45CH
Term AI4 Sel
H3-14
Gain (terminal AI4)
Sets the input gain (level) when
terminal AI3 is 10 V. Set
according to the 100% value
selected in H3-13.
0.0 to
1000.0
100.0%
Yes
A
A
45DH
Term AI4 Gain
H3-15
Bias (terminal AI4)
Sets the input gain (level) when
terminal AI3 is 0 V. Set accord-
ing to the 100% value selected
in H3-13.
-100.0
to
100.0
0.0%
Yes
A
A
45EH
Term AI4 Bias
H3-16
Analog input filter
time constant
Sets primary delay filter time
constant in seconds for the four
analog input terminal
(AI1,AI2,AI3,AI4).
Effective for noise control etc.
0.00 to
2.00
0.00
s
No
A
A
45FH
Filter Avg Time
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
d3-01
Jump frequency 1
Set the center values of the
jump frequencies in %.
This function is disabled by set-
ting the jump frequency to 0
Hz. Always ensure that the fol-
lowing applies:
d3-01
≥
d3-02
≥
d3-03
Operation in the jump fre-
quency range is prohibited but
during acceleration and decel-
eration, speed changes
smoothly without jump.
0.0 to
100.0
0.0%
No
A
A
2F0H
Jump Freq 1
d3-02
Jump frequency 2
0.0 to
100.0
0.0%
No
A
A
2F1H
Jump Freq 2
d3-03
Jump frequency 3
0.0 to
100.0
0.0%
No
A
A
2F2H
Jump Freq 3
d3-04
Jump frequency width Sets the jump frequency band-
width in %.
The jump frequency will be the
jump frequency ± d3-04.
0.0 to
100.0
1.0%
No
A
A
2F3H
Jump Bandwidth
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display