![YASKAWA FSDrive-MV1S Instructions Manual Download Page 134](http://html1.mh-extra.com/html/yaskawa/fsdrive-mv1s/fsdrive-mv1s_instructions-manual_3478741134.webp)
6
-10
Acceleration and Deceleration Characteristics
This section explains the acceleration and deceleration characteristics of the Inverter.
Setting Acceleration and Deceleration Times
Acceleration time indicates the time taken for the output frequency to climb from 0% to 100%. Deceleration
time indicates the time taken for the output frequency to reduce to 0%. The factory setting of the acceleration
time is C1-01, and the factory setting of the deceleration time is C1-02.
Related Parameters
Constant
Number
Name
Description
Setting
Range
Fac-
tory
Setting
Change
during
Opera-
tion
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
C1-01
Acceleration time 1 Sets the acceleration time to accelerate
from 0 to the maximum output fre-
quency, in 1-second units.
0.0 to
6000.0
60.0 s
Yes
Q
Q
240H
Accel Time 1
C1-02
Deceleration time 1 Sets the deceleration time to deceler-
ate from the maximum output fre-
quency to 0, in 1-second units.
120.0 s
Yes
Q
Q
241H
Decel Time 1
C1-03
Acceleration time 2 The acceleration time when the multi-
function input “accel/decel time 1” is
set to on.
60.0 s
Yes
A
A
242H
Accel Time 2
C1-04
Deceleration time 2 The deceleration time when the multi-
function input “accel/decel time 1” is
set to on.
120.0 s
Yes
A
A
243H
Decel Time 2
C1-05
Acceleration time 3 The acceleration time when the multi-
function input “accel/decel time 2” is
set to on.
60.0 s
No
A
A
244H
Accel Time 3
C1-06
Deceleration time 3 The deceleration time when the multi-
function input “accel/decel time 2” is
set to on.
120.0 s
No
A
A
245H
Decel Time 3
C1-07
Acceleration time 4 The acceleration time when the multi-
function input “accel/decel time 1”
and “accel/decel time 2” are set to on.
60.0 s
No
A
A
246H
Accel Time 4
C1-08
Deceleration time 4 The deceleration time when the multi-
function input “accel/decel time 1”
and “accel/decel time 2” are set to on.
120.0 s
No
A
A
247H
Decel Time 4
C1-11
Accel/decel time
switching fre-
quency
Sets the frequency for automatic
acceleration/deceleration switching.
Below set frequency:
Accel/decel time 4
Above set frequency:
Accel/decel time 1
The multi-function input “accel/decel
time 1” or “accel/decel time 2” take
priority.
0.0 to
100.00
0.00%
No
A
A
24AH
Acc/Dec SW Freq