![YASKAWA FSDrive-MV1S Instructions Manual Download Page 133](http://html1.mh-extra.com/html/yaskawa/fsdrive-mv1s/fsdrive-mv1s_instructions-manual_3478741133.webp)
Stopping Methods
6-
9
Changing the DC Injection Brake Current Using an Analog Input
If you set H3-05 (Multi-function Analog Input Terminal AI2 Function Selection), H3-09 (Multi-function Ana-
log Input Terminal AI3 Function Selection), or H3-13 (Multi-function Analog Input Terminal AI4 Function
Selection) to 6 (DC injection brake current), you can change the DC injection brake current level using the
analog input.
At 10 V input (voltage) or 20 mA input (current), 100% of the Inverter rated current will be applied.
Fig 6.7 DC Injection Brake Current Using an Analog Input
Using an Emergency Stop
Set a multi-function input terminal (H1-
) to 6F or 70 (emergency stop) to coast to a stop. If inputting the
emergency stop with an NO contact, set the multi-function input terminal (H1-
) to 6F, and if inputting the
emergency stop with an NC contact, set the multi-function input terminal (H1-
) to 70.
DC injection brake voltage level
Inverter rated current