C.8 Message Examples
236
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
u
Writing to Multiple Registers
Function code 10h allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process
works similar to reading registers, i.e., the address of the first register that is to be written and the data quantity must be
set in the command message. The data to be written must be consecutive so that the register addresses are in order,
starting from the specified address in the command message. The data order must be high byte, then lower byte.
The following table shows an example of a message where a forward operation has been set with a frequency reference
of 60.0 Hz for the slave 1 drive.
If parameter values are changed using the Write command, depending on the setting of H5-11, an Enter command will be
necessary to activate the data or save them.
Refer to H5-11: Communications ENTER Function Selection on page 230
and
Refer to Enter Command on page 252
for detailed descriptions.
Note:
For the number of bytes in the command message, take double the number of the data quantity.
Command Message
Response Message (normal)
Response Message (fault)
Slave Address
01H
Slave Address
01H
Slave Address
01H
Function Code
10H
Function Code
10H
Function Code
90H
Starting No.
Upper
00H
Starting No.
Upper
00H
Error Code
02H
Lower
01H
Lower
01H
CRC-16
Upper
CDH
Data Quantity
Upper
00H
Data Quantity
Upper
00H
Lower
C1H
Lower
02H
Lower
02H
Number of Bytes
04H
CRC-16
Upper
10H
Starting Data
Upper
00H
Lower
08H
Lower
01H
Next Data
Upper
02H
Lower
58H
CRC-16
Upper
63H
Lower
39H
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...