6.3 Periodic Maintenance
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
197
Pe
ri
od
ic
In
spe
ct
io
n
&
Main
tenan
ce
6
Table 6.4 Performance Life Monitors Used for Component Replacement
n
Related Drive Parameters
Use parameters o4-03, o4-05, o4-07, and o4-09 to reset a Maintenance Monitor to zero after replacing a specific
component.
NOTICE:
If these parameters are not reset after the corresponding parts have been replaced, the Maintenance Monitor function will
continue to count down the performance life from the value that was reached with the old part. If the Maintenance Monitor is not reset,
the drive will not have the correct value of the performance life for the new component.
Parameter
Component
Contents
U4-03
Cooling Fan
Displays the accumulated operation time of the fan from 0 to 99999 hours. This value is automatically reset
to 0 after it reaches 99999.
U4-04
Displays the accumulated fan operation time as a percentage of the specified maintenance period.
U4-05
DC Bus Capacitors Displays the accumulated time the capacitors are used as a percentage of the specified maintenance period.
U4-06
In-rush Prevention
Circuit Breaker
Counts the number of ON/OFF operations for the in-rush prevention circuit breaker, and displays the
maintenance period as a percentage [%].
U4-07
IGBT
Displays the percentage of the maintenance period reached by the IGBTs.
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...