3.2 Standard Connection Diagram
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
81
E
lec
tr
ic
al In
st
al
lat
io
n
3
u
Class: 11 kV
Figure 3.5
Figure 3.5 Drive Standard Connection Diagram (Example: CIMR-MV2
H
HA035)
Main circuit power supply,
AC 3-phase
11 kV
50/60 Hz
Ground resistance:
less than 10 Ω
Control power supply,
AC single-phase
200/220 V
50/60 Hz
RC
SC
Input voltage Input current
Output
voltage
Frequency reference
4 to 20 mA DC
Cooling fan power supply
Controller power supply
M
Output frequency
4 to 20 mA DC
Output current
4 to 20 mA DC
Analog output: 4 points
-10 V to +10 V
Phases-A/B/Z input
CN4-1
Analog input: 2 points
-10 V to +10 V
Digital input: 8 points
Digital output 8 points
CN21, 22
CN4-2
CN14-1
AO_1
GND
FG
1
2
3
AO_2
GND
FG
1
2
3
CN13-1
AI_1
GND
FG
CN13-2
1
2
3
ISO
AMP
Current detection
Resistance board
ISO
AMP
ISO
AMP
ISO
AMP
ISO
AMP
L4
L6
L5
L7
L8
L9
L1
L3
L2
Main circuit input
terminals
Main circuit output
terminals
Grounding of the
main circuit
terminal EA
Control power supply
terminals
Analog input terminals
Analog output
terminals
1
2
3
R
S
T
R
S
T
R
S
U
W
V
CN14-2
Ground resistance:
less than 100 Ω
Grounding of the
control system
terminal ED
CN10-1
RS-232
CN10-2
USB
USB
RS-485
(option)
CN10-3
MC ON
Relay circuit
CN9
MC ANS
Terminals for inrush current
suppression circuit (option)
26
28
27
L48
L47
DI
DO
CN14-3
1
2
3
1
2
3
CN14-4
Digital output: 8 points
(Option)
Digital output: 8 points
Digital input: 8 points
CN12-2
CN11-2
Complementary PG
board (option)
I/O or communication
board (option)
(Option)
(Option)
(Option)
Phases-A/B/Z input
Line driver PG board
(option)
Digital operator
USB copy unit (option)
RJ-45
DriveWizard Plus MV
RJ-45
RS-232
From expansion PLC board (option)
Panel board
Relay
board
(option)
Single-phase
200/220 Vac
Contact input
terminals
Contact output
terminals
Medium-voltage
Primary panel on
Operation interlock
13
4
3
14
1
2
15
Stop
command
Run
command
Relay circuit
Reserved
External fault
reset
Reserved
CN1
1-1
6
5
8
7
10
9
Major fault
During run
Drive ready
Minor fault
Medium-voltage
Power shutdown
Command
E
E
CN12-1
30
31
32
33
34
35
36
37
38
39
40
Relay board
Output
(form-C
contact)
I/O
Relay circuit
Complementary
output PG
Line driver
output PG
PG
L19
L20
L21
L22
L23
L24
L25
Phase-A signal
Phase-B signal
Ground
PG
L19
L20
L21
L22
L23
L24
L25
Phase-A dignal
Phase-B signal
Ground
12 V or 5.5 V
±
5%,
max. 200 mA
12 V
±
5%,
max. 200 mA
Either one or two boards are
installed by setting parameter.
PLC
L71
RS485
L72
L73
L74
Reserved
45
44
42
41
43
Asia
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...