4.4 Start-Up Flowcharts
122
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
u
Subchart A-2: High Performance Operation Using OLV or CLV
Subchart A-2 describes the setup procedure when using Open Loop Vector Control or Closed Loop Vector Control.
Vector control is appropriate for applications requiring a high starting torque and torque limits.
Note:
Although the drive sets parameters for the PG encoder during Auto-Tuning, sometimes the direction of the motor and direction
of the PG get reversed. Use parameter F1-05 (PG1 Rotation Direction Setting) to switch the direction of the PG to match the
motor direction.
Figure 4.10 High Performance Operation Using OLV or CLV
Figure 4.10
<1> Ensure that the brake is released.
Is
the motor
cable longer than 50
meters?
YES
NO
From
Flowchart
A
<1>
YES
YES
NO
Run the machine and check for desired operation.
Perform Stationary Auto-Tuning.
(T1-01 = 2)
Possible for disconnect
the motor from the machine?
Is the load less than
30% of the rated load
for the motor?
Perform Rotational
Auto-Tuning (T1-01 = 0).
Return to
Flowchart
A
Energize main circuit power.
NO
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...