C.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
245
M
EMOBUS
/Mo
dbu
s
Co
m
m
u
ni
ca
ti
on
s
C
00C9H
Alarm Contents 3
bit 0
Speed Deviation (dEv)
bit 1
PG Disconnect (PGo)
bit 2
Reserved
bit 3
MEMOBUS/Modbus Communication Error (CE)
bit 4
Option Communication Error (bUS)
bit 5
Serial Communication Transmission Error (CALL)
bit 6
Motor Overload (oL1)
bit 7, 8
Reserved
bit 9
Option Card External Fault (EF0)
bit A
Motor Switch during Run (rUn)
bit B
Reserved
bit C
Serial Communication Transmission Error (CALL)
bit D
Undertorque Detection 1 (UL3)
bit E
Undertorque Detection 2 (UL4)
bit F
MEMOBUS/Modbus Test Mode Error (SE)
00CAH
Alarm Contents 4
bit 0, 1
Reserved
bit 2
External Fault at contact input terminal 9 (EF9)
bit 3
External Fault at contact input terminal 10 (EF10)
bit 4
External Fault at contact input terminal 11 (EF11)
bit 5
External Fault at contact input terminal 12 (EF12)
bit 6
PID Feedback Loss (FbL)
bit 7
Excessive PID Feedback (FbH)
bit 8
Reserved
bit 9
Drive Disabled (dnE)
bit A
PG Hardware Fault (PGoH)
bit B to F
Reserved
00CBH
Alarm Contents 5
bit 0 to 3
Reserved
bit 4
Cooling Fan Maintenance Time (LT1)
bit 5
Capacitor Maintenance Time (LT-2)
bit 6, 7
Reserved
bit 8
External Fault at contact input terminal 1 (EF1)
bit 9
External Fault at contact input terminal 2 (EF2)
bit A, B
Reserved
00CCH
Alarm Contents 6
bit 0 to 3
Reserved
bit 4
IGBT Maintenance Time (90%) (TrPC)
bit 5
Soft Charge Bypass Relay Maintenance Time (LT-3)
bit 6
IGBT Maintenance Time (50%) (LT-4)
bit 7 to F
Reserved
00CDH
Alarm Contents 7
bit 0 to 2
IGBT Maintenance Time (90%) (TrPC)
bit 3
Input Overvoltage (IOV)
bit 4 to F
Reserved
00CEH
Alarm Contents 8
bit 0 to 2
Reserved
bit 3
Battery Voltage Low (BAT)
bit 4 to 7
Reserved
bit 8
Transformer Temperature Fault (TMA1)
bit 9, A
Reserved
bit B
Voltage Unbalance (VUB)
bit C
External Fault at contact input terminal 13 (EF13)
bit D
External Fault at contact input terminal 14 (EF14)
bit E
External Fault at contact input terminal 15 (EF15)
bit F
External Fault at contact input terminal 16 (EF16)
00CFH
Reserved
Register No.
Contents
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...