5.6 Operator Programming Error
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
171
T
ro
ubles
hoo
ting
5
Settings for N.C. and N.O. input for the following
functions were selected simultaneously:
• External Search Command 1 and External Search
Command 2 (61 vs. 62)
• Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
• Motor Switch Command and Accel/Decel Time 2
(16 vs. 1A)
• FWD Run Command (or REV) and FWD/REV Run
Command (2-wire) (40, 41 vs. 42, 43)
• Motor Switch Command and Up 2/Down 2 Command
(16 vs. 75, 76)
• Check if contradictory settings have simultaneously been assigned to the contact
input terminals.
• Correct the contact input settings.
One of the following settings was entered while H1-
=
2 (External Reference 1/2):
• b1-15 or b1-16 set to 3 but no option card is connected
• b1-15 = 1 (Analog Input) and H3-02 (Analog Input
Function Selection) is not set to 0 (Analog Frequency
Reference).
H2-
= 38 (Drive Enabled) but H1-
is not set to 6A
(Drive Enable) and 70 (Drive Enable 2).
A signed value (H3-01) is set for the analog input while
allocating the UP2/DOWN2 commands (75 and 76).
Cancel either setting.
Digital Operator Display
Error Name
oPE05
Run Command/Frequency Reference Source Selection Error
The setting for executing a Run command or frequency reference from communication
option card input is not correct.
Cause
Possible Solutions
Frequency reference is assigned to an option card
(b1-01 = 3) and an input option card is not connected to
the drive.
Reconnect the input option card to the drive.
The Run command is assigned to an option card
(b1-02 = 3) and an input option card is not connected to
the drive.
Although the digital card input is set for BCD special for a
5-digit input (F3-01 = 6), the data length is set for 8-bit or
12-bit (F3-03 = 0, 1).
Set the input data for 16 bit (F3-03 = 2)
The following values have been set while an AI-A3 option
card is installed:
• The source of frequency reference setting is assigned to
an option card (b1-01 = 3).
• The action for the analog card is set for separate
terminal input (F2-01 = 0).
Make sure parameters are set properly.
The content below is set at the same time but AI-A3
option is not connected:
• b1-16 (Run Command Selection 2) = 3 (Option card)
• H1-
= 2 (External reference 1/2 selection)
Make sure parameters are set properly.
Digital Operator Display
Error Name
oPE06
Control Method Selection Error
Correct the setting for the control method.
Cause
Possible Solutions
A control mode has been selected that requires a PG
option card to be installed
(A1-02 = 3), but no PG option card is installed.
• Connect a PG option card.
• Correct the value set to A1-02.
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...