P1015 TEST R.BOOST
G
P1015 TEST R.BOOST
10.0 %
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Sets the motor starting voltage (possible setting 0 -25%) as a percentage of the rated
input voltage.
P1020 TEST R.TIME
G
P1020 TEST R.TIME
5 sec
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Sets the time for the test run.
P1025 SEL.DEVICE
P1025 SEL.DEVICE
* 1 *
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Selects the inverter for the manual test run.
P1030 TEST RUN MAN.
P1030 TEST RUN MAN.
Press > for 3 sec
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Performs a manual test run for the unit selected by P1025 SEL.DEVICE: this function is also
valid for fixed-speed pumps in Cascade relay mode.
For this parameter please note that, once entered into edit mode (by pressing the
provided push button), the user can confirm the new value by pressing for 3 sec the right
(
►
) push button.
8.3.15 M1100 SETUP
MENU SCOPE
This submenu includes the following software parameters:
• Restore factory setting
• Password 2
• Clear error memory
8 Programming
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual
87