P918 OFFSET Y2
P918 OFFSET Y2
0.00 bar
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Set the required pressure at this flow rate.
For an example of the offset function and more information, see
Example: P900
SUBMENU OFFSET
(page 105).
8.3.14 M1000 TEST RUN
Menu scope
This submenu includes the following software parameters:
• Automatic test run
• Test run frequency
• Test run boost
• Test run time
• Selecting Inverter for test run
• Manual test run
P1005 TEST RUN
G
P1005 TEST RUN
After 100 hrs
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Controls the automatic test run, which starts up the pump after the last stop, to prevent
the pump from blocking (possible setting are "Off" or "After 100 hrs".
Automatic test run is only active when both of the following occur:
• HYDROVAR is stopped but manually released.
• The external ON/OFF contact (X1/18 - 19) is closed.
P1010 TEST RUN FRQ.
G
P1010 TEST RUN FRQ.
30.0 Hz
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Sets the frequency for manual and automatic test run.
8 Programming
86
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual