P710 ANALOG OUT.2
P710 ANALOG OUT.2
Actual value
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Selects the second analog output, which is connected to terminal X3/5-6 on the Premim
Card (analog output 4 – 20 mA = 0 - 100%).
P715 CONF.REL.1
P715 CONF.REL.1
Running
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Selects the status relay 1 (X2/4 - 5 - 6). Possible settings are:
Setting
Description
Action if status = YES
Power
HYDROVAR is connected to the power
supply.
Relay 1: X2/ 4 - 6 closed
Running
The motor is running
Relay 1: X2/ 4 - 6 closed
Errors
An error is indicated on HYDROVAR
(including power failure).
Relay 1: X2/ 5 - 6 closed
Warnings
A warning is indicated in the
HYDROVAR
Relay 1: X2/ 5 - 6 closed
StandBy
The pump is released manually and
by external release, no error/warning
is indicated and the HYDROVAR does
not run.
Relay 1: X2/ 4 - 6 closed
Errorreset
If the parameter P615 ERROR RESET
is activated and a warning occurs five
times - > Error - >
Relay 1: X2/ 4 - 6 closed
P720 CONF.REL.2
P720 CONF.REL.2
Errors
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Selects the status relay 2 (X2/1 - 2 - 3). Possible settings are:
Setting
Description
Action if status = YES
Power
HYDROVAR is connected to the power
supply.
Relay 2: X2/ 1 - 3 closed
Running
The motor is running
Relay 2: X2/ 1 - 3 closed
Errors
An error is indicated on HYDROVAR
(including power failure).
Relay 2: X2/ 2 - 3 closed
8 Programming
80
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual