This parameter sets the pressure control mode for the pump system (single and multi
pump): depending on the setting ("Constant" or "Differential") a set of further parameters
are automatically configured.
Whenever P1311 CONTROL MODE is set to a new value, each parameter in the below
table is overwritten to its own specified value, regardless of previous different settings.
P1311 = Constant
P1311 = Differential
P225 RAMP 3
70 sec
90 sec
P230 RAMP 4
70 sec
90 sec
P250 MIN.FREQ.
20 Hz
25 Hz
P255 CONF.FMIN
f -> 0
f -> fmin
P260 FMIN TIME
0 sec
3 sec
P315 HYSTERESIS
80%
90%
P410CONF.SENSOR
Sensor 1
Sens.1 - Sens.2
P1312 DIMENSION UNIT
Selects the unit of measure for the system.
P1312 DIMENSION UNIT
bar
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
For further information, see
P405 DIMENSION UNIT
(page 71)
P1313 START-UP COMPLETED?
P1313 START-UP COMPLETED?
No
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
If the application the is a multi-pump, then the startup procedure for the first [N-1] pumps
is stopped here when selecting Yes.
If the application the is a single-pump or the last pump of a Multi-pump, then select No .
P1314 SENSOR RANGE
P1314 SENSOR RANGE
20mA - 10.00bar
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Sets the end range value (20 mA or 10 V) of the connected sensor. In particular, the end
range value (20 mA or 10 V) must be always equal to the 100% of the sensor range (that is,
for a 0.4 bar differential pressure sensor, is 20 mA=0.4 bar).
8 Programming
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual
95