Voltage
supply
HVL
Fuse
Circuit
breaker
UL
Non UL
Bussmann
Edison
Littelfuse
Ferraz-
Shawmut
Fuse
ABB
Type T
Type gG
MCB S200
3~ 230 VAC
3.015
JJN-15
TJN (15)
JLLN 15
A3T15
16
S203-C16
3.022
JJN-15
TJN (15)
JLLN 15
A3T15
16
S203-C16
3.030
JJN-20
TJN (20)
JLLN 20
A3T20
16
S203-C20
3.040
JJN-25
TJN (25)
JLLN 25
A3T25
25
S203-C25
3.055
JJN-30
TJN (30)
JLLN 30
A3T30
25
S203-C32
3.075
JJN-50
TKN (50)
JLLN 50
A3T50
50
S203-C50
3.110
JJN-60
TJN (60)
JLLN 60
A3T60
63
S203-C63
3~ 380–460
VAC
4.015
JJS-10
TJS (10)
JLLS 10
A6T10
10
S203-C10
4.022
JJS-10
TJS (10)
JLLS 10
A6T10
10
S203-C13
4.030
JJS-15
TJS (15)
JLLS 15
A6T15
16
S203-C13
4.040
JJS-15
TJS (15)
JLLS 15
A6T15
16
S203-C16
4.055
JJS-20
TJS (20)
JLLS 20
A6T20
20
S203-C20
4.075
JJS-20
TJS (20)
JLLS 20
A6T20
20
S203-C25
4.110
JJS-30
TJS (30)
JLLS 30
A6T30
30
S203-C32
4.150
JJS-50
TJS (50)
JLLS 50
A6T50
50
S203-C50
4.185
JJS-50
TJS (50)
JLLS 50
A6T50
50
S203-C50
4.220
JJS-60
TJS (60)
JLLS 60
A6T60
63
S203-C63
Type gG fuses in the table are reporting the fuses rated current.
Residual Current Devices, RCDs (GFCIs)
Where Ground Fault Circuit Interrupters (GFCIs) and residual current devices (RCDs), also
know as earth leakage circuit breakers (ELCDs), are used, comply with the following:
• for HVL 2.015 ÷ 2.040, use GFCIs (RCDs) which are capable of detecting AC currents
and pulsating currents with DC components. These GFCIs (RCDs) are marked with the
following symbol:
• for HVL 3.015 ÷ 3.110 and 4.015 ÷ 4.220, use GFCIs (RCDs) which are capable of
detecting AC and DC currents. These GFCIs (RCDs) are marked with the following
symbols:
• Use GFCIs (RCDs) with an inrush delay to prevent faults due to transient earth currents.
• Dimension GFCIs (RCDs) according to the system configuration and environmental
considerations.
NOTICE:
When an earth leakage circuit breaker or ground fault circuit interrupter is selected, the
total leakage current of all the electrical equipment in the installation must be taken into
account.
6 Electrical Installation
28
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual
Summary of Contents for hydrovar