P430 SENS.1 CAL.0
This parameter is used to calibrate the minimum value of Sensor 1.
P430 SENS.1 CAL.0
0 %
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
After setting P405 DIMENSION UNIT and P420 SENSOR RANGE, the zero point for this
sensor can be adjusted between -10 % and +10 %.
P435 SENS.1 CAL.X
This parameter is used to calibrate the upper range value of sensor 1.
P435 SENS.1 CAL.X
0 %
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
After setting P405 DIMENSION UNIT and P420 SENSOR RANGE, the upper range value
can be adjusted between -10 and +10%.
P440 SENS.2 CAL.0
This parameter is used to calibrate the minimum value of Sensor 2.
P440 SENS.2 CAL.0
0 %
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
After setting P405 DIMENSION UNIT and P420 SENSOR RANGE, the zero point for this
sensor can be adjusted between -10 % and +10 %.
P445 SENS.2 CAL.X
This parameter is used to calibrate the upper range value of sensor 2.
P445 SENS.2 CAL.X
0 %
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
After setting P405 DIMENSION UNIT and P420 SENSOR RANGE, the upper range value
can be adjusted between -10 and +10%.
8.3.9 M500 SEQUENCE CONTR.
MENU SCOPE
In this submenu it is possible to configure parameters for running a multi-pump system.
This submenu includes the following software parameters:
8 Programming
74
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual