• Offset (X1, Y1)
• Offset (X2, Y2)
For an example of the offset function and more information, see
Example: P900
SUBMENU OFFSET
(page 105).
P905 OFFS.INPUT
P905 OFFS.INPUT
OFF
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Selects the offset input. Possible setting are:
Setting
Offset calculation
Off
Disabled
An. U1 0-10V
Calculated from the voltage signal (0 - 10 V) connected to
the terminals X3/7-8-9 (Required Value 1)
An. U2 0-10V
Calculated from the voltage signal (0 - 10 V) connected to
the terminals X3/10-11-12 (Required Value 2)
An. I1 0-20mA
Calculated from the current signal (0 - 20 mA) connected
to the terminals X3/7-8 (Required Value 1)
An. I1 4-20mA
Calculated from the current signal (4 - 20 mA) connected
to the terminals X3/7-8 (Required Value 1)
An. I2 0-20mA
Calculated from the current signal (0 - 20 mA) connected
to the terminals X3/10-11 (Required Value 2)
An. I2 4-20mA
Calculated from the current signal (4 - 20 mA) connected
to the terminals X3/10-11 (Required Value 2)
If the incoming current signal drops to below 4 mA, a warning message is shown on the
display; however, HYDROVAR continues to operate without the offset function.
P907 OFFSET RANGE
P907 OFFSET RANGE
100
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Set the representation of the sensor range: the value depends on the maximum range of
the connected offset sensor. A higher offset range gives a higher signal input resolution.
For an example of the offset function and more information, see
Example: P900
SUBMENU OFFSET
(page 105).
P910 LEVEL 1
P910 LEVEL 1
0
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
8 Programming
84
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual